Messages and lights work because the panel only shows what the PLC already wrote. A typed number waits for your program to take it: Enter sets the DA bit and leaves the value in entry register V2000. One rung moves V2000 into your application register on that bit, then sets the Data Acknowledge bit so the panel clears DA and accepts the next entry.
Messages and lights working while a typed number goes nowhere is the normal first state of a keypad panel, not a broken one. Text and lamps are display functions the panel handles on its own. A typed number waits for your program to take it. When the operator presses Enter, the panel sets its data-available bit, named DA in the panel's manual, and leaves the value in the entry register V2000 that this configuration assigns. One rung watches DA, moves V2000 into the register your logic reads, and answers with the Data Acknowledge bit so the panel clears DA and accepts the next entry. Build that rung and the number arrives.
What the panel does when you press Enter
The manual for this class of two-line, 20-character operator panel documents a four-step cycle for numeric entry:
- The operator types digits on the numeric keypad and they show on the entry line. Nothing has reached the PLC.
- Enter. The panel writes the value into the entry register assigned to the entry module, V2000 in this configuration, and sets the DA bit in its status register. The manual documents this bit as the signal to the PLC program that data has been entered.
- Your rung moves V2000 into your application register. This is the step your program owns, and the step that is missing when messages work and numbers do not.
- Your rung sets the Data Acknowledge bit. The panel clears DA and allows new data entry, and the manual requires the acknowledge bit cleared once DA has dropped.
Three jobs, three owners: the message prompts the operator, the panel reports a completed entry, the PLC copies it. The prompt never does the copy. The arrow keys only navigate the display; Enter starts the handoff because it is the key press that sets DA.
Symptoms and what each one points to
- The prompt shows, the arrow keys navigate, the application value never moves. The display path is healthy and no rung is taking the entry. Add the rung below.
- V2000 shows 12 after Enter but your register stays put. The move rung is missing, never enabled, aimed at the wrong destination, or overwritten a scan later. Monitor both registers across one Enter and the failing step shows itself.
- The first entry lands and the second does nothing. DA is still set. The panel holds new entries until the Data Acknowledge bit clears DA, so finish step 4 of the cycle.
- Your register takes 12, then drifts back to the old value. A second rung is writing the destination. Cross-reference the destination address in your programming software.
Check the entry path before editing the machine logic
- Put the machine where a changed register can do no harm: outputs disabled or the machine out of cycle. The value you are about to move lands in a register the machine logic reads.
- Show the entry message, type 12, press Enter.
- Watch V2000 and the DA bit. Expected result: V2000 = 12 and DA = 1.
- If V2000 never takes the value, stop at the panel. The entry register assignment lives in the panel's configuration software, and the mapping to verify is between the entry module and its V-memory address. If the address refuses to tag at all, work through fixing HMI invalid address errors when tagging PLC memory before going further.
The rung: one move on DA, then the acknowledge
Build it from five elements:
- A contact on the DA bit from the panel's status register.
- A one-shot on that contact, so one Enter produces one move.
- A move instruction with source V2000 and your application register as destination.
- A SET of the Data Acknowledge bit on the same one-shot.
- A RESET of the acknowledge bit driven by a normally closed DA contact, so it drops after the panel clears DA.
In structured text, with the panel's documented names and yours separated:
Entry_DA : BOOL // documented: the DA bit in the panel status register
Ack : BOOL := FALSE // documented: the Data Acknowledge bit
Entry_Reg : INT // documented: the entry register, V2000 in this configuration
Preset_Dest : INT := 8 // yours: the application register this example writes
IF rising_edge(Entry_DA) THEN
Preset_Dest := Entry_Reg; // the move
Ack := TRUE; // answer the panel
END_IF;
IF NOT Entry_DA THEN
Ack := FALSE; // required once DA has dropped
END_IF;
That is the pattern; substitute the two documented bits and the register from your own configuration printout. Two additions are worth making while you are in the ladder: a range check on the moved value, and the correct wiring when the destination is a counter preset. Clamping HMI numeric entry limits in PLC ladder logic covers the range check, and loading counter presets from an HMI into a counter module covers the counter case.
Worked example: entering 12 into a timer preset
The application register Preset_Dest holds 8 and feeds a timer with a 0.1 s time base, so the machine currently runs 8 x 0.1 s = 0.8 s. The operator types 12 and presses Enter.
| Step | Action | V2000 | DA | Ack | Preset_Dest |
|---|---|---|---|---|---|
| 0 | start | 0 | 0 | 0 | 8 |
| 1 | type 12, press Enter | 12 | 1 | 0 | 8 |
| 2 | move fires on the DA edge | 12 | 1 | 1 | 12 |
| 3 | panel sees Ack, clears DA | 12 | 0 | 1 | 12 |
| 4 | rung resets Ack | 12 | 0 | 0 | 12 |
| 5 | type 47, press Enter | 47 | 1 | 0 | 12 |
| 6 | move fires again | 47 | 1 | 1 | 47 |
Step 2 is the fix: 12 replaces 8 in Preset_Dest, and with the 0.1 s base the timer runs 12 x 0.1 s = 1.2 s. Step 5 is the proof: a second, different value through the same path rules out a stale register or a display-only change. If step 1 leaves V2000 at 0, the fault is upstream in the panel configuration. If step 2 leaves Preset_Dest at 8, the fault is the rung.
If the setpoint also needs an audience
The keypad stays the input device. When the entered setpoint also has to be readable across the floor, that becomes a one-way display decision: live factory data display, signage or dashboard walks the choice, and shop-floor screens playing content from a card cover the read-only case.
Recommendation: wire the move to the rising edge of DA from entry register V2000, finish the handshake with the Data Acknowledge bit, and prove the path with entries of 12 then 47 while the machine outputs are disabled. Only then return the terminal to the machine.
Questions
Why does the first entry work and the second one do nothing?
The panel holds off new entries until the handshake finishes. Your rung must set the Data Acknowledge bit after the move; the panel then clears DA and accepts the next number. Once DA has dropped, clear the acknowledge bit so the cycle is ready. A move that runs every scan is no substitute, because DA going set is the only new-data signal the panel gives you, and with DA stuck set the panel will not take the next number.
Where exactly is the entered number before the move?
In the entry register assigned to the numeric entry module, V2000 in this configuration, with the DA bit in the panel's status register. The prompt message and the entry line on the two-line, 20-character display are display objects, and they hold no value the PLC can read. If V2000 never takes the typed value, the fault is in the panel configuration, upstream of any PLC rung you could write.
What if DA sets and V2000 holds 12 but my register never changes?
The panel side is finished and the fault is in the PLC. The move rung is missing, its enable condition is false, its destination is the wrong address, or a later rung overwrites the destination after the move. Cross-reference the destination address, force the DA bit once with the machine outputs disabled, and watch the destination. Change one thing at a time so a wrong mapping stays visible.
Do the arrow keys send anything to the PLC?
On a panel of this class the arrow keys select and edit the entry line on the display. The transfer to PLC memory happens on Enter, the only key press that sets DA. Message display and lamp functions need no PLC-side rung at all, which is exactly why text and lights can work while numeric entry does not.
Planning information, not legal or engineering advice. Rules differ by place: check codes and permits with your local authority and your licensed trades.