Small HMI panels give static text and text entry objects a fixed pixel window with no scrolling. Split the screen: list channels by number and short code, and open one dedicated edit screen where the full stored name takes the whole width. On a 640 x 480 panel that changes the visible name from about 13 characters to about 40.
A 6-inch HMI panel cannot scroll long alarm names inside static text or text entry objects, so the fix is layout. Split the job in two screens: the channel list shows a number, a short code and the values operators scan, and one dedicated edit screen gives the selected channel's full stored name the whole width of the panel. The names stay in the PLC where they already are; only the screens change. Below is the sizing math for a 51-channel panel, the build steps, and the checks that prove the binding is right.
What the panel gives you
Published specifications for 6-inch class panels list 320 x 240 and 640 x 480 pixels. The resolution decides how much text fits; the diagonal only names the class. The static text and text entry objects on these panels publish no scrolling option in their properties, so each object is a fixed window: the characters that fit its pixel width are all the operator sees. A longer string in the PLC adds no pixels.
Open your object properties once and look. If your software version lists a scroll or marquee behavior for the object, test it with a string longer than the field before trusting it. If nothing is listed, design for fixed windows. When a line of text truly has to move, the movement can come from logic that shifts a window of characters into an ordinary string display; the build is in scrolling text on an HMI screen with PLC logic.
On the 320 x 240 version of the panel, the inch-based sizing below yields the same character counts, rendered coarser.
Why shrinking the font stops working
Operators stand at the machine, close enough to touch it, about 3 ft from the glass. Planning figures for legible text say 30 ft of viewing distance per inch of capital height for unhurried reading, and 20 ft per inch for fast reading. Use 20 for a panel someone reads while working: 3 ft divided by 20 ft per inch gives 0.15 in of capital height as the floor. That floor pins the character size, so the count of characters a row can show comes from row width alone. Once the name entry shares a row with three or four editable values, only the leftover width remains for the name.
The layout that works
Two screens do the whole job.
The overview lists all 51 channels in pages: channel number, a short code you assign once, and the two or three values operators scan. No name entry lives on this screen. Selecting a channel opens the edit screen.
The edit screen is one screen, not 51. The title shows the selected channel's number, a full-width text entry holds that channel's stored name, and below it sit the editable fields for the same channel. One back button returns to the list. Every field binds through the selected channel's index, so adding channel 52 is a data change in the PLC with no new screen to draw. Showing a stored name beside fixed objects uses the same binding approach as showing a saved name on an HMI screen with static buttons.
Example layout: 51 alarm channels on a 640 x 480 panel viewed at 3 ft
Inputs:
- 51 alarm channels, names stored as strings in the PLC.
- Panel 640 x 480 pixels on a 6 in diagonal, 4:3 shape.
- Viewing distance 3 ft, an operator at the machine.
- 20 ft per inch of capital height for fast reading, row pitch 1.7 x capital height, character advance about 0.75 x capital height. All three are planning figures; digits and capitals dominate a name field.
Rule in words: size the capitals from the viewing distance, convert to pixels with the panel's pixel density, then divide each field's width by the character advance.
Arithmetic:
- Capital height: 3 ft / 20 ft per inch = 0.15 in.
- Active width of a 4:3 panel with a 6 in diagonal: 6 x 4 / 5 = 4.8 in. Pixel density: 640 px / 4.8 in = 133 px per inch.
- Capital height in pixels: 0.15 in x 133 px per inch = 20 px.
- Row pitch: 1.7 x 20 px = 34 px. Character advance: 0.75 x 20 px = 15 px.
- Usable list height: 480 px - 34 px header - 34 px footer = 412 px, and 412 / 34 = 12.1, so 12 rows per page.
- Pages for 51 channels: 51 / 12 = 4.25, so 5 pages with the last holding 3 channels.
- Name entry sharing the row: 640 px - 60 px channel number - 3 x 120 px editable values - 20 px padding = 200 px, and 200 / 15 = 13 characters.
- Name entry on the edit screen: 640 px - 2 x 20 px margins = 600 px, and 600 / 15 = 40 characters.
The shared row holds 13 characters; the edit screen holds 40, three times the characters from the same panel. The threshold: once the longest stored name passes what the shared row shows, 13 characters here, name editing moves to the edit screen. Set the project's string length to what the edit screen shows, 40 characters here, so storage and display agree.
Building it, step by step
You need the panel project, the PLC holding the 51 name strings, and one integer register to carry the selected channel's index.
- Check the object properties once for a scroll or marquee setting on your static text and text entry objects. Nothing listed means fixed windows; design for them.
- Keep each channel's name in its own stored string field, addressed from one base with the index as offset. The write-up on stored fields versus packed HMI bytes covers why unpacked fields pay off when a panel has to index dozens of them.
- Draw the overview at the example sizing: 12 rows per page at a 34 px pitch, columns for number, short code and scan values, page buttons for the 5 pages. The mechanics of the picker are in building an HMI text menu with a screen selector list.
- Draw one edit screen: channel number in the title, the full-width name entry across the top, the channel's editable fields below, one back button.
- Bind every edit-screen field through the selected index, using the addressing your project already uses. The name entry reads and writes the selected channel's stored string; each value field reads and writes that channel's data.
- Type with the panel's on-screen keyboard. On panels this small, the layout in a paged keypad for text entry on a small HMI keeps a long name comfortable to enter.
- Commit on confirm: the name writes when the operator presses save, and the back button returns to the list with the row refreshed.
How to check it worked
Run these in the panel runtime with the PLC online:
- Select the channel with the longest name, open the edit screen, and read the whole name against the PLC register, to the last character.
- Enter a test name at the full string length you configured, save, navigate away, return, and confirm the stored value persists.
- Edit one channel's name, then open the next channel and confirm its name and values are untouched. A wrong index binding edits the wrong alarm channel, so this cross-check gates production use.
- Page through every list page and confirm the selection highlight follows the touched row.
Recommendation: Keep the overview for scanning and selection, and give all 51 channels one shared edit screen bound through the selected index. On a 640 x 480 panel, move name editing off the shared row as soon as the longest name passes 13 characters at 20 px capitals; the edit screen then shows 40. Cap the stored string length at the same 40 so the field and the PLC agree.
Questions
Is there a way to scroll the name inside the entry object?
Check the object properties in your software version; this panel class lists no scrolling behavior for static text or text entry objects. Some runtimes clip the overflow silently and some wrap to a second line, so test with a string longer than the field before trusting either. For text that must move, shift a window of characters from PLC logic into an ordinary string display.
Do I need one edit screen per channel?
No. Build one edit screen and bind its fields through the selected channel's index; the title displays the number and the name entry points at the selected string. Separate screens are worth drawing only when different channels expose different fields, for example when one group carries an extra threshold. Then group the channels and give each group its own edit screen.
How do I stop two operators editing names at the same time?
On a single panel it cannot happen, since one screen serves one touch at a time. With a second panel or a SCADA node writing the same strings, gate the edit screen with a PLC bit: the first station to open the screen sets the bit, the write commits on confirm, and the bit clears on exit. Other stations show the data as view only while the bit is set.
What if the longest name still does not fit the edit screen?
At the example sizing the edit screen shows about 40 characters across 640 px. A 10.1 in class panel at 1024 x 600 shows roughly 70 with the same capital-height rule, so one size up covers most naming schemes. Short of that, cap the naming convention at what the screen shows and keep the long wording in the channel documentation.
Planning information, not legal or engineering advice. Rules differ by place: check codes and permits with your local authority and your licensed trades.