After a factory default reset, some HMI panels lose the built-in web server's default HTML files, and a firmware reload or a fresh project download does not bring them back. Check the Built-in_Flash folder over FTP against the eight expected files, then restore a matched set from a known-good panel or the panel maker's technical support.
A factory default reset on an HMI touch panel clears the settings you expect and, on some panel families, strips the built-in web server's default HTML files along with them. The web server keeps answering, so the panel looks healthy until you need a remote page and every link lands on a not-found page. A firmware reload does not bring the files back, and neither does a fresh project download, so the usual repair loop costs hours and fixes nothing. This article walks the fault end to end: the symptom, the two services to enable, the FTP check over TCP port 21, the eight default files a healthy folder holds, and the two recovery paths that work.
Why does a factory reset delete the panel's web server files?
On the panel family in this fault, a factory default reset wipes the default HTML files from Built-in_Flash alongside the settings it is meant to clear, leaving only the busy and not-found status pages behind. The default pages live in the panel's own storage, separate from the runtime firmware and from the application project, and the reset removes them with everything else it resets.
The maker's own remote access documentation treats the HTML set as something a reset rewrites: it tells you to back up a custom index file before a reset if you want to keep it. Treat that as the rule for the whole set. If a file in Built-in_Flash matters to you, it lives outside your project backups, so copy it off the panel before you reset.
A reset is also one of several events that strip content from these panels: a power cycle can drop the project itself, and that fault has its own checks.
What does the fault look like on the floor?
The web server still opens, so the panel looks healthy on the floor. The fault shows up when every browser link lands on the not-found page, sometimes days after the reset that started it. The operator interface on the panel itself keeps working, which is exactly why the missing files go unnoticed until someone needs remote access.
| What you see | What it points to | What to do next |
|---|---|---|
| Every browser link lands on the not-found page | The default page set is incomplete | List Built-in_Flash over FTP |
| The FTP listing shows only an images folder, ws_busy.html and ws_notfound.html | The reset deleted the default files | Restore the file set (below) |
| A firmware reload finished and the files are still missing | The reload carries no complete HTML set on this family | Stop re-flashing and restore the files |
| A project download finished and the files are still missing | The project carries screens, not web files | Restore the file set (below) |
| The FTP client cannot connect at all | A service or network problem, not missing files | Fix FTP access first, then judge the folder |
Which settings do you enable before you inspect the panel's storage?
Turn on two services before you judge the file set: the Web Server service and the FTP Server service, both found under Touch Panel Network in the panel's Setup menus. Then download the project so the panel is in its normal running state. A browser that opens the panel's home page tells you the web service runs; only the FTP listing tells you which files survived.
With both services on, connect an FTP client to the panel and open Built-in_Flash. If the client cannot log in, fix access first: an access failure looks identical to an empty folder, and you would repair the wrong thing.
Write down the model and the firmware revision the panel reports now. Support will ask for both, and it is the same revision check you make before a project transfer.
Which eight files should the web folder contain?
A complete set is 8 HTML files: fancyscreen, filelist, index, instructions, screendisplay, screenlist, ws_busy and ws_notfound, sitting in the Built-in_Flash folder structure with the images folder beside them. Once FTP access works, the listing and count take about 15 minutes. Check the listing against these names:
- fancyscreen
- filelist
- instructions
- screendisplay
- screenlist
- index
- ws_busy
- ws_notfound
The panel's listing may print the .html extension on some names and not others; the case report abbreviated most names without it. Compare names the way the listing prints them and never rename a file to match an abbreviation. Keep names, extensions and the folder layout exactly as you find them when you compare or transfer files.
If the listing shows all 8 names but the browser still fails, the files are fine: check the address and path you type into the browser and the state of the web service instead.
Worked example: what is missing when Built-in_Flash shows three items?
After a factory reset on the panel in this case, running firmware 1.21 Build 06.16, an FTP listing of Built-in_Flash returned 3 items: the images folder, ws_busy.html and ws_notfound.html, so 6 of the 8 default HTML files were gone. The listing looked like this:
Built-in_Flash
root
images
ws_busy.html
ws_notfound.html
The arithmetic: a healthy folder holds 8 default HTML files, the listing holds 2 files, so 8 - 2 = 6 files missing: fancyscreen, filelist, index, instructions, screendisplay and screenlist. The panel had already been through the full standard loop before this count was taken: firmware reloaded from file EA121616.eas, then a new blank project with the web and FTP services enabled pushed to the panel. The listing came back identical after each step.
The result is a web server that answers requests but has no default pages to serve, short by 6 files. Two reloads and one project download have already failed to change the count, so the decision the numbers point to is a file restore. The firmware version and file name belong to that specific panel; match your own model and firmware before you request or transfer anything.
Why does a firmware reload not bring the files back?
Because neither operation carries the default HTML set on this panel family: in the reported case a full firmware reload with file EA121616.eas and a fresh blank project with both services enabled left the folder exactly as the reset had emptied it. Firmware service updates the runtime. A project download sends the application screens. The web pages are a third payload stored beside them, and once the reset has removed them, neither routine puts them back.
One theory holds that firmware installs the HTML files only when they are absent, which would predict the files reappear on the next reload; in the reported case they did not, so the theory earns no place in a repair plan. Check the directory and repair by restoring files.
A panel that goes quiet after a firmware update has a different fault with its own checks, starting with communication rather than this folder.
How do you restore the default HTML files?
Two recoveries worked in practice: copy the 8 files over FTP from a known-good panel of the same model and firmware, or ask the panel maker's technical support for a set matched to your exact model and firmware revision when no second panel exists. Run it as a sequence:
- Pick the donor panel: same model, same firmware revision, a complete set, and its own web pages serving correctly.
- Connect an FTP client to both panels and open Built-in_Flash on each.
- Copy the 8 HTML files, plus the images folder, from the donor to your panel, keeping names, extensions and folder layout exactly.
- Refresh the destination listing and count the files against the 8 names; confirm the files arrived on the panel, not just in the transfer queue.
- If you have only one panel, request the default set from the panel maker's technical support with your model, firmware revision and FTP listing attached, then transfer it the same way.
- Keep a copy of the restored set off the panel, filed with the project records.
Do not repeat the factory reset to test the repair: the reset is the action that deletes these files, and on a running machine it also takes the operator interface and its settings down with it. Schedule any reset you cannot avoid.
Recommendation: treat every factory default reset on an HMI panel as an event that can strip the web server files. Before the panel returns to the machine, list Built-in_Flash over FTP and check for all 8 default HTML files; when the count comes up short, restore a matched set from a same-model panel or the panel maker, and hold off on further firmware reloads until the files are in place.
If you are fitting a separate notice or status screen beside the machine, see our factory and shop-floor displays.
How do you check the repair before the panel goes back on the machine?
Confirm the count first, then the pages: refresh the FTP listing and check all 8 default HTML names are present in Built-in_Flash, then open the web server from a browser and confirm the default pages load instead of the busy or not-found pages. Three checks, in order:
- The FTP listing shows all 8 names in Built-in_Flash.
- A browser opens the default pages and moves between them.
- The panel runs its production project, not the blank one used for diagnosis.
A reset returns settings to their defaults too, so anything customized comes back empty. Re-download the production project and set the startup screen again before the panel mounts back on the machine.
If the listing is complete and the pages still fail, capture the directory listing, the panel model, the firmware revision and the exact browser result, and send that package to support. That combination points to a page-serving problem with the files present, and it needs the panel's own documentation to take further.
Questions
Are the eight default HTML files the same on every HMI panel?
No. The eight names and the Built-in_Flash folder come from the panel family in this fault. Other panel families keep different files in different storage locations, so never transfer a set between different models. Ask for files matched to your panel's exact model and firmware revision, and compare the transferred listing against your panel's documented default set before you close the job.
How do I keep the web files safe through the next reset or update?
Copy the restored eight-file set off the panel and store it with the project records. If you customize index.html, back it up before any reset or firmware update. The panel maker's remote access documentation treats the HTML set as something a reset rewrites, and says the only way to keep a custom index file is to back it up first.
What should I send when I ask the vendor for replacement files?
Send the panel model, the firmware revision exactly as the panel displays it, and a capture of the Built-in_Flash FTP listing. The case behind this article involved firmware 1.21 Build 06.16 and a reload file named EA121616.eas; identifiers like those tell support which file set matches your panel. Ask for the complete default HTML set for your model, not a partial one.