CODESYS CANopen node status and guard timer explained

5 min read · Published November 3, 2026

CODESYS CANopen has no documented per-message receive flag. The implicit variables give supervision: pCanOpenNode[i].nStatus, where 5 means operational, and GuardTimer.Q for a heartbeat or Node Guard timeout. Read those two fields for node health, and watchdog the mapped process data when you need proof one message arrived.

CODESYS CANopen gives you node supervision, not a message-received flag. The CANopen implicit variables publish the state of the master and of every node: pCANopenMaster for the master, one pCanOpenNode[i] entry per node. Two fields do the daily work. nStatus holds the node's NMT state, and 5 means operational. GuardTimer.Q goes TRUE when the node stops answering heartbeat or Node Guard supervision. This page says what each field means, what the numbers are, how fast a dead node shows up, and what to do when the question is really about one message.

The implicit variables

CANopen implicit variables are globals the CANopen library declares for you; you read them, you never declare them. pCANopenMaster covers the master. pCanOpenNode is the node array, sized by the library constant MAX_NODEINDEX, and each entry carries the fields supervision needs: nStatus, ucNodeNbr, and GuardTimer. The exact member list moves between runtime releases, so open the reference installed with your copy. On a V2.3 install that is the CANopen runtime PDF in the Documents/English folder, titled CANopen for 3S Runtime Systems. The move itself is ordinary library work, the same one you make when you read an I2C register from a CODESYS function block: find the window onto the hardware and read it every cycle.

What nStatus tells you

nStatus carries the node's NMT state in the CiA 301 coding: 5 operational, 4 stopped, 127 pre-operational, 0 boot-up. A node exchanges process data only in the operational state, so 5 is the number a running machine should show. 4 means the node was sent an NMT stop command. 127 is the state after power-up or reset, before the master starts the node.

The library's own example tests for any value other than 5, and that is the right test:

FOR i := 0 TO MAX_NODEINDEX DO
    IF pCanOpenNode[i].nStatus <> 5 THEN
        xNodeFault := TRUE;
        uiFaultNode := pCanOpenNode[i].ucNodeNbr;
        EXIT;
    END_IF
END_FOR

The array index is not the node number; that is what ucNodeNbr is for. Keep EXIT when one fault is enough to stop the machine. Drop it and collect every hit into an array when the operator needs the whole list on one screen. Run the scan every PLC cycle; it costs one comparison per entry.

When every entry faults in the same cycle, one cause sits behind all of them: the master, its cable, or its supply. Before you walk the line, check if a CODESYS runtime is running or stopped on the controller.

GuardTimer.Q and the two supervision protocols

CANopen supervises nodes with two mechanisms, heartbeat and node guarding, and GuardTimer.Q covers both. With the heartbeat protocol, each node transmits one byte, its state, on COB-ID 0x700 plus its node number, at a producer interval you configure. The master only listens. The intent, as the CiA 301 error control protocols set it out, is that every participant on the bus shows it is still available and still in its intended NMT state.

Node guarding works the other way around: the master polls each node once per guard time, the node answers with its state, and bit 7 of that answer toggles on every reply so a repeated answer is visible. The slave watches the polls as well. Life time is guard time times life time factor: 200 ms x 3 = 600 ms, after which an unpolled slave raises its own communication error.

GuardTimer.Q is TRUE when the entry's supervision timed out: heartbeats that stopped, or a guard poll that was never answered. nStatus shows the last state the node reported, so on a node that went quiet the timer trips while the status still holds the old value. Treat the timer as the trip signal and the status as the last known state.

Example: six nodes on a palletizer

A palletizer cell runs six CANopen nodes: two drives, three remote I/O blocks, one print-mark encoder. Each node produces a heartbeat every 500 ms, and the master's consumer timeout is 750 ms, the common 1.5 x 500 ms. Pull the CAN lead off the second drive, node number 4, right after one of its heartbeats, and count.

That heartbeat left at t = 0. Nothing follows it. At t = 750 ms the consumer times out and the entry's GuardTimer.Q goes TRUE. The cycle scan then finds the first nStatus other than 5, sets xNodeFault, and copies ucNodeNbr = 4 into uiFaultNode. From cable out to fault on the panel: about three quarters of a second, with the node number attached. Plug the lead back in, the next heartbeat lands within 500 ms, the timer resets, and the entry reads 5 again. Latch the fault with your own one-shot so somebody acknowledges it.

The numbers scale straight. A 200 ms producer time with a 300 ms timeout detects in about 300 ms; 1000 ms with a 1500 ms timeout takes about one and a half seconds. Choose the producer time from how fast the machine can damage product or tooling when a drive stops talking, not from the bus baud rate.

When you need a message-received flag

Supervision answers whether the node is alive. It carries one state byte about the node and nothing about your process data, so it cannot stand in for a receive flag on one message. When the question is whether one data object is updating, watch the data itself.

The mapped PDO variable is already in your program. Time it. A drive position that should change every 10 ms and has held still for 50 ms is stale, whatever the node status says. When the value can legitimately sit still, have the slave append a free-running counter to its transmit PDO and reset a timer on every change of the counter. That check is yours, it is per message, and it trips on exactly the object you care about.

Slow SDO traffic is a third fault family. If supervision is clean and SDO transfers still stall, CANopen SDO block transfer support and troubleshooting covers that path before you touch the wiring.

Showing the fault list on the floor

The node number on the machine HMI tells the operator. A list of the line's dead nodes on a wall screen tells maintenance where to walk first, and that second job is a display job, not an HMI job: factory status display or operator HMI draws the line, and shop-floor status screens cover what a screen on the floor has to survive. Once the scan names the drive, PLC fault code decoding for drive diagnostics tells you why it went quiet. Keep an event history and the same data feeds both screens: log PLC variables to a database from CODESYS is the storage side.

What to set

Recommendation: Run heartbeat supervision on every new machine: 500 ms producer time, 750 ms consumer timeout, one scan of pCanOpenNode for nStatus other than 5 every cycle, and GuardTimer.Q latched as the fast fault bit. Use node guarding only for legacy slaves that cannot produce a heartbeat. When one data object must provably update, add the counter to its transmit PDO and time it in the PLC, and keep that check separate from node supervision.

Questions

Is there a CODESYS CANopen message received flag?

Not in the implicit variables. The documented members cover supervision: nStatus holds the node's NMT state and GuardTimer.Q goes TRUE when heartbeat or Node Guard supervision times out. No member of those structures is documented as a per-message receive indicator. For one data object, map a free-running counter into the transmit PDO and time its changes in the PLC.

What does nStatus 5 mean in CODESYS CANopen?

5 is the CiA 301 code for the NMT operational state, the only state in which a node exchanges process data. 4 is stopped, 127 is pre-operational and 0 is boot-up. Expect 127 for a moment after a node powers up or resets. The library's example treats any value other than 5 as a fault, which is the right test for a running machine.

Heartbeat or node guarding: which should I use?

Heartbeat, wherever the slaves support it. Each node transmits on its own and the master only listens, so there is no polling load on the bus and any device can watch the producer. Node guarding needs the master to poll every node once per guard time and check the toggle bit, which suits legacy slaves that cannot produce a heartbeat.

How quickly will a dead CANopen node be detected?

Detection time is your supervision timeout, measured from the last good message. At a 500 ms producer time with a 750 ms consumer timeout the fault shows about 750 ms after the last heartbeat. Node guarding is similar: a 200 ms guard time with a life time factor of 3 gives a 600 ms life time before the slave flags the master as gone.

Where are the CANopen implicit variables documented?

In the CANopen runtime manual installed with your CODESYS version. On a V2.3 install, look for the CANopen for 3S Runtime Systems PDF in the Documents/English folder. The member list differs between runtime releases, so read your installed copy before wiring a member into fault logic, and note whether a flag is latched until cleared or refreshed each cycle.