Log PLC variables to a database from CoDeSys

7 min read · Published November 2, 2026

No, the CoDeSys runtime does not write database records. You add a client that reads variables from the runtime over OPC or DDE and inserts rows: OPC for process data, DDE only for values changing slower than about once per second. Commission one variable end to end, then scale.

A CoDeSys runtime will run your IEC 61131-3 program every shift, but it will not write a single database row. The write belongs to a client: a program on a PC that reads variables from the runtime over OPC or DDE and inserts them into Microsoft Access or any engine that accepts inserts. This page maps that path, picks the link, and commissions one variable end to end, so the first row lands in your table with a value you watched change at the controller.

Can CoDeSys write variable values straight into a database?

No, the CoDeSys runtime cannot write a database row itself: it executes the program and serves variable values to a data interface, and a separate client on a PC reads those values and writes the rows. Every working setup you will ever see puts that client in the middle, and the client is the piece you configure.

Three paths cover the job:

Path What reads the runtime What writes the rows Pick it when
OPC client The client, through the OPC server the runtime provides The same client, or a logger behind it Process data, fast or slow, tag lists that grow
DDE A DDE-capable application through the CoDeSys data interface That same application A few values changing slower than about one change per second
Custom program Your own code through any interface the runtime offers Your own code Acquisition and insert rules that must fit together exactly

A custom program, written in a language such as Visual Basic, is the honest answer when acquisition and insert logic must be built together: one codebase reads the runtime and writes the records. For everything else, an OPC client or a DDE-capable application already does both jobs.

Draw the path on one page before you touch the program: runtime, interface, client, database file, and the machine each piece runs on. When a logging project stalls, that drawing usually names the component somebody assumed somebody else was supplying.

Use OPC for anything that changes faster than about once per second or that will grow past a handful of tags; use DDE only for a few slow values where a DDE-capable application already sits on the desk. OPC earns the default spot because the client can browse the tag list, subscribe so the server pushes changes, and carry a timestamp and a quality flag with every value. DDE is one conversation per value: workable on a desk, thin on a plant floor.

Where user management is active on the controller, the OPC UA server asks the client for a user name and password before the session opens, so create that account before commissioning day.

Recommendation: put an OPC UA client between the runtime and the database whenever a tag changes faster than about once per second or the tag list will grow; keep DDE for a few slow values feeding one application on one desk PC, and write a custom program only when no client offers the logic you need.

What do you need before you start?

Four things: a running runtime with its data interface enabled, a client PC on the same network with the client software installed, a database file with a table ready for rows, and one PLC variable whose value you can watch change. Get all four on the bench before any protocol work.

  • On the controller: the program running, the OPC server enabled in the runtime configuration (or the DDE interface enabled), and the target variable published.
  • On the PC: the client installed, and the LAN path to the controller checked with your site's normal tools.
  • In the database: a table on a drive the client can write, with fields for the value, the time, and the tag name.
  • On paper: the sample rule, periodic or on change, and the login the client will use. Give that login read-only access to the variables; a logger has no business writing to a running process.

Choose the first variable deliberately: a counter or a clock you can force to move, so a frozen read shows itself in seconds.

How do you commission the first record?

Expose one changing variable, read it in the client, map it to one field, force one write, and inspect the row. One variable keeps interface errors and mapping errors from hiding behind each other, so the first record takes minutes, not days.

  1. Enable the OPC server (or the DDE interface) in the runtime configuration and load that configuration so the interface is live.
  2. In the client, connect to the server and browse to the variable. Watch the client's live value move while you force the PLC value.
  3. Create the table if it is not there yet: value, timestamp, tag name. Keep the timestamp mandatory and everything else simple.
  4. Map the one variable to the value field and let the client fill the timestamp and the tag name.
  5. Trigger one write with whatever the client offers: a manual write command, a one-shot sample, or a forced change.
  6. Open the table and read the row against the client's displayed value at that same moment.
  7. Break the link on purpose and confirm the client reports a read fault; the table must gain no rows while the link is down.

Reads fine, inserts nothing: the fault is in the database connection, the file permissions, the field mapping, or the insert path. Inserts fine, value wrong or frozen: the fault is upstream, so check the variable selection, the subscription, and whether the interface is enabled but delivering nothing.

What does a worked example look like on one pump station?

A pump station logs a seconds-of-runtime counter into the database every 5 seconds; three shifts a day produce 17,280 rows, and the arithmetic below is the whole sizing job. Run it once with your own sample period and the storage question is answered before the first row exists.

  • Sample period: 5 s.
  • Production day: 3 shifts x 8 h = 24 h = 86,400 s.
  • Rows per day: 86,400 / 5 = 17,280.
  • Rows per 30-day month: 17,280 x 30 = 518,400.
  • Size: four short fields, about 60 bytes of data a row. 518,400 x 60 B is about 31 MB of raw data. With file overhead and one index on the timestamp, budget 100 MB a month and the table stays manageable for years.

That table doubles as content for a shop-floor status screen: export the last shift as a table image, load it on the offline display from its card, and the board updates as often as the export runs. The factory data table signage layout rules cover the image, a rolling 24 hour runtime display shows the same counter as it accumulates, and whether that board needs live values or a daily export is its own call: live factory data display walks it. Size the text before you build anything: 30 ft of viewing distance per inch of capital height is the FHWA planning figure, and 20 ft per inch is the safer pick where people glance. The screen size and viewing distance guide turns that into a panel size.

How fast can you log before the path breaks?

One sample per tag per second is comfortable for a client and a database file on one PC, and OPC UA on a healthy LAN holds a 100 ms publishing interval, 10 samples a second, before the insert becomes the bottleneck. A single-row insert into a local database file costs a few milliseconds, so a 10-row-per-second stream swamps a one-row-at-a-time writer. Batch tens of rows into one write and the same writer keeps up. Log on change with a deadband when values sit still for hours; a quiet signal then writes almost nothing.

Target rate Path that holds it What to watch
One row per 10 s or slower DDE or OPC Nothing special
One row per second per tag OPC Insert time; batch as the tag list grows
10 rows per second OPC UA, 100 ms publishing interval Database writes; batch rows in tens

How do you check the whole path works?

Follow one value through every hop while it changes: the variable in the program, the live read in the client, the inserted row, and the row still present after the database closes and reopens; then run a 15-minute soak. End commissioning only after all five checks pass.

  • Live read: force a change at the controller and see it in the client within one sample period.
  • Row integrity: the stored value equals the client's displayed value at that sample, and the timestamp advances by the sample period.
  • Fault behavior: with the link down, the client raises a read fault, the table gains no rows, and rows resume with honest timestamps when the link returns.
  • Persistence: close and reopen the database; the soak's rows are still there.
  • Soak: 15 minutes at the intended rate. At a 10 s sample, expect 900 / 10 = 90 rows. Count them.

The decision, case by case: fast tags or a growing list, an OPC UA client plus the database; a few slow values on one desk, DDE; bespoke acquisition logic, a custom program. Commission one variable end to end before the list grows.

Questions

Does the CODESYS Automation Server replace a logging client?

No. The Automation Server manages controllers centrally: roles, access rights, user accounts, and automatic notifications. It reaches PLCs on a local network through the CODESYS Edge Gateway, which also serves as a remote gateway. It is a management layer. You still need a client that reads variables and writes the database rows.

Should the client speak OPC DA or OPC UA?

Choose UA when the runtime offers it. The OPC Foundation maintains conformance profiles for Data Access, built on the part of the UA specification that defines how automation data is represented, so a certified client and a certified server interoperate. Keep DA only where an older server or an older client is already installed and working.

When is OPC UA PubSub worth adding?

PubSub publishes values to subscribers instead of answering client reads one at a time. It earns its place when several systems consume the same fast stream at once, for example a logger, an analyzer, and a dashboard. For one logging PC, ordinary client reads are simpler and give up nothing.

Can you log over a serial link instead of the network?

Yes, for slow values. A CODESYS Gateway on the PC side can reach a runtime over an RS232 cable, and a DDE-capable application such as a spreadsheet takes its values from that gateway. Serial suits a handful of slow tags on one desk; the network path serves everything faster.

Planning information, not legal or engineering advice. Rules differ by place: check codes and permits with your local authority and your licensed trades.