When every web admin submenu answers Requested content is not available, the controller's root filesystem is usually full. In the documented case the runtime update tool left its .deb install packages on a flash of about 240 MiB. Run df, delete the retained packages or run Reset Origin Device, and upgrade the runtime to 3.5 SP15 or later.
When every submenu in a controller's web admin answers "Requested content is not available", read it as a full root filesystem first. In the documented case the flash the controller boots from was 100% used with nothing free, and the CODESYS applications went on running the whole time, so the fault stayed hidden until a routine job needed the web admin and could not load its pages. The cause was a bug in the runtime deployment: the update tool copies its Debian install packages onto the controller and never removes them. This article gives the df check that confirms the diagnosis, the arithmetic behind it, the two documented cleanups, and the upgrade that ends the bug.
Symptoms and what each points to
Match your controller against this list before changing anything.
- Every submenu answers "Requested content is not available" while a basic page, such as the firmware display, still loads. The web server is answering, so the service itself is running; the documented cause sat one level down, on the disk.
- Applications keep running. The runtime was executing normally while the pages failed, so storage is the suspect. Confirm it anyway with the CODESYS runtime running-or-stopped check before you touch the filesystem.
- The fault appeared after weeks of normal use. Retained install packages accumulate one runtime deployment at a time, so a flash that filled gradually matches this timing.
- A network change exposed it. The fault surfaced in the documented case when a NIC IP address needed changing, a job many controllers reach only through the web admin.
A dark panel screen on the controller itself is a different trail; start from the embedded controller video display checks.
Confirm the full filesystem with df
All of this runs over SSH from a laptop, the same access you use to provision an embedded module with no display attached.
- Open an SSH session to the controller. The shell answers even when the web admin does not.
- Run
dfand find the row whose mount point is/. Skip the rows for/boot,/homeand the temporary filesystems; the root row is the one that matters. - Read the Use% and Available columns on that row. The fault reads 100% used and 0 available. The runtime vendor's diagnosis for the exact web admin message was shorter still: no free space left.
- Run
dfagain after each cleanup step to confirm the space returned.
The same SSH session also reaches cbm, the controller's console-based management tool, for the jobs the web pages normally handle.
Example: a 240 MiB root filesystem at 96 percent after cleanup
The inputs, each with its source:
| df column | Value | What it is |
|---|---|---|
| Filesystem | /dev/root | The flash the controller boots from |
| 1K-blocks | 245679 | Total size, about 240 MiB |
| Used | 222880 | Blocks holding data |
| Available | 9692 | Blocks free for writing |
| Use% | 96 | The figure df prints |
| Mounted on | / | The root row |
Every value comes from the controller's df output after the Reset Origin cleanup. Before the fix, the same row read 100% used with no space available.
The rule in words: df computes Use% as used blocks divided by usable blocks, and usable blocks are used plus available. The 1K-blocks total is larger than that sum because the filesystem reserves a slice of its blocks for the root account, and df leaves that slice out of the percentage.
The arithmetic:
- Usable blocks: 222880 + 9692 = 232572.
- Use%: 222880 ÷ 232572 = 0.9583, so 95.8%, which
dfrounds to the 96 it prints. - Free space: 9692 blocks × 1024 bytes per block = 9,924,608 bytes, about 9.5 MiB.
- Headroom: 100 - 96 = 4 percentage points above full.
Result: the reset left about 9.5 MiB free on a flash that had been completely full, and the web admin pages loaded again at that level.
Decision: a root row at 100% used with 0 available is the fault, and freeing root space is the fix; once the row reads below 100% and the pages load, the job is done. Reset Origin reached exactly this 96% row. Deleting the retained packages frees more, and the expected level for that route is given with the fix below.
Delete the retained install packages
The update tool deploys the runtime as Debian packages and leaves those install files on the controller after they are installed; that was the vendor's own diagnosis of the bug. Each deployment on an affected runtime leaves another set, and the sets add up on a small flash.
- List the retained files:
find /root -name 'codesys*.deb' -ls. Each hit should be a runtime install package, a name that starts with codesys and ends in .deb. - Delete the files the listing shows, giving the full path for each one.
- Run
dfagain. The documented procedure lands at about 89-90% used on the flash. - Open the web admin and load the submenu that failed. Pages loading is the confirmation.
The controller in this case ran runtime version 3.5.14.30 when its flash filled. The cleanup is a stopgap: the vendor marked the bug solved with the 3.5 SP15 runtime, so the packages return with the next deployment until you upgrade.
Fallback: Reset Origin Device
If the listing comes back empty and the root row still reads 100%, use the reset. Right-click the controller entry in the device tree, the same tree you work in when you fix a runtime device mismatch safely, and choose Reset Origin Device.
Reset Origin Device deletes every file the CODESYS tools downloaded to the controller, which includes what the deployment put there. Keep your project archive and the runtime installer in hand and plan to redeploy after the reset. In the documented case the reset took the root row from completely full to the level in the example above, and the web admin came back.
After the reset, run df and confirm the row reads below 100%, then load the submenu that failed.
Keep it from coming back
- Upgrade the runtime to 3.5 SP15 or later. The retained-package bug is reported solved from that release on.
- Run
dfafter every runtime deployment. On affected versions, each deployment leaves a new set of install packages, so usage climbs toward 100% one update at a time. A root row creeping past 90% is the early warning. - Budget the flash. The whole root filesystem in this case was about 240 MiB, so moving to a fixed runtime protects more space than any cleanup.
Recommendation: If the root row reads 100% used with 0 available, list and delete the retained codesys .deb packages first and confirm the row drops below 100%; run Reset Origin Device when the row still reads 100% after that, accept the redeploy it requires, and take the runtime upgrade that stops the packages coming back.
Questions
Why does a disk problem show up as a content message in the web admin?
The message is the web admin's answer for a page it cannot produce. In the documented case the runtime vendor traced it to a single cause: no free space left on the flash. With zero blocks available on the root filesystem, no submenu page could be served, while the basic firmware display and the running applications carried on. The df check in the article turns that message into a yes-or-no answer within a minute.
How do I reach management functions while the web admin is down?
Open an SSH session and run cbm, the controller's console-based management tool. It prints the controller details the web pages normally show: product description, order number, license information and firmware revision, followed by its own menu. In the documented case it answered while every web admin submenu failed, and it was the path given for jobs such as changing a NIC IP address. Run df first all the same, so you know whether storage is the reason the pages are out.
Is a full root filesystem the only cause of this message?
In the documented case it was the only cause found: the vendor tied the message directly to no free space left, and freeing space brought the pages back. The df check in this article separates the two cases. If the root row shows room free, below 90% used for example, and the message still appears, the flash is not the cause; the documented evidence here ends there, and the next step belongs with the runtime vendor's support channel.