Yes. The CODESYS counterpart of a Studio 5000 Add-On Instruction is the function block: one interface, stored state per instance, called once per task cycle, with no import path, so you re-enter the parameters and logic from the AOI definition and the driver documentation. Translate one-shot rungs to R_TRIG and verify each transition with the amplifier enable off.
Yes, there is an equivalent, and you can build it yourself. In CODESYS the counterpart of a Studio 5000 Add-On Instruction is the function block: a named unit with inputs, outputs and its own stored state. It is defined in IEC 61131-3, the PLC language standard that CODESYS implements. Your Oriental Motor AZD-AEP already connects and exchanges data from CODESYS, so the network side of this job is finished. What the supplier packaged as a jog AOI you now rebuild as a function block. Nothing imports. The work is three parts: copy the interface, translate the sequence, and verify the result against the driver documentation with the motor unable to move.
What the function block gives you
A function block is a program organization unit in IEC 61131-3, usable in any of the standard's five languages. You declare it once, then instantiate it. Every instance keeps its own copy of the block's internal variables between calls, so the state of one axis never touches another. The task that runs your program calls the block once per cycle. That single fact is what makes one-shot rungs translate differently, as the example below works through. Where you place the call in the task chain changes what the block sees each cycle, so trace the PLC execution order across task layers once before you trust the translation.
| Studio 5000 element | CODESYS element |
|---|---|
| Add-On Instruction | FUNCTION_BLOCK |
| Input parameter | VAR_INPUT |
| Output parameter | VAR_OUTPUT |
| InOut parameter | VAR_IN_OUT |
| Local tag | Variable declared inside the block |
| One-shot rung | R_TRIG instance called every cycle |
| One AOI call per axis | One instance per axis |
What you need before you write code
Three documents, and without all three you stop:
- The AOI definition: the logic itself if the project includes it, or at minimum the parameter list with data types and the read or write direction of each.
- The jog command for the AZD-AEP from the driver communication documentation: which data item starts the jog, which value means idle, which feedback confirms motion.
- The tag mapping from the supplier's Studio 5000 example, which shows how the AOI parameters line up with driver data.
The supplier's jog example is written for Studio 5000, and the AZD-AEP speaks EtherNet/IP, so the same data items are visible to CODESYS. Being able to read and write a data item does not identify it as the jog command. The command and its idle value come from the documentation or the AOI logic. If your package has neither, request both from the supplier's support channel before you write anything that can move the slide.
Rebuild the AOI in six steps
- Write the interface down first. Open the AOI definition and list every Input, Output and InOut parameter with its data type. Mark each one read, written or both, and note the driver data item behind it. With only an example project and no AOI logic, stop at this step until the supplier sends the definition.
- Create the block and mirror the interface. One
FUNCTION_BLOCK, withVAR_INPUT,VAR_OUTPUTandVAR_IN_OUTsections that match the AOI parameters one for one. Give every parameter that Studio 5000 set at configuration time a default value in its declaration. - Translate the logic one rung at a time. Keep the sequence and the interlocks in the same order. Every rung that fires once per request gets an
R_TRIGinstance declared inside the block and called every cycle. - Keep the driver mapping in its own layer. A separate block, or a clearly bounded section, that moves the outputs to the AZD-AEP data items named in the documentation and reads the documented feedback back. This layer is where the idle value is written on release.
- Instantiate once per axis. One instance variable per axis, each called every cycle from the same task. If the axis count changes while the machine runs, create function block instances dynamically instead.
- Carry over stop, reset and fault handling. Take these from the AOI logic and the driver documentation, with the drive's fault and status feedback wired to outputs you can watch.
Example: one jog tap through a 10 ms task
This is the translation most rebuilds get wrong, so work it with numbers.
Inputs, with their sources:
- Task cycle time: 10 ms, read from the task settings in your project. Yours may be 5 ms or 20 ms; the arithmetic here uses 10 ms.
- Operator tap on the jog input: 200 ms, a deliberate press on a pendant button.
- Behavior to reproduce, from the AOI logic: one jog command write per press, and the documented idle value written when the input falls.
The rule in words: the task calls the block once per cycle, so the calls during one tap equal the tap length divided by the cycle time. An R_TRIG output is TRUE on the one call that sees the input change from FALSE to TRUE, and FALSE on every call after. Code guarded by that edge runs once per tap. Code that tracks the input runs on every call.
The arithmetic:
- 200 ms / 10 ms = 20 calls while the button is held.
- With the
R_TRIGguard: 1 of those 20 calls writes the jog command. - Without it: all 20 calls write the command, and any counter or step number inside the block advances 20 times per tap.
Decision: an action the AOI fires once per request gets an R_TRIG in front of it. One write per tap is the signature to look for later in the watch table. The release path stays plain: the code that writes the idle value when the button is released must look at the input level on every cycle, with no edge guard.
Check the rebuild with the motor unable to move
Run every check below with the amplifier enable off and the slide guarded.
- At rest, the command output sits at the documented idle value.
- One tap produces exactly one command write, the signature from the example, and the documented feedback changes after it.
- Release produces the documented stop response within the next cycles.
- A simulated drive fault clears only through the path the AOI used.
- After a warm restart or a fresh download, no jog request is latched: the instance starts at the idle value.
Force the jog input true and false from the watch table to walk every transition without touching the pendant; how CoDeSys forcing works in the PLC cycle covers the rules a forced value follows. If nothing in the watch view changes at all, check whether the CODESYS runtime is running or stopped before you debug logic that may be fine. Only then enable the amplifier and make the first live moves with the machine's commissioning controls.
When the jog still misbehaves
- Reads work but nothing moves: the mapping layer writes nothing, or writes a data item that is not the documented jog command. Compare the idle and command values against the manual.
- Jogs but does not stop: the release path is missing, or it writes the wrong idle value.
- One tap fires the command many times: the
R_TRIGguard is missing, or the block is called from two places. - Works after a download, then sticks or dies: the instance was reinitialized, or a retained variable did not return to idle.
Recommendation: Rebuild the jog AOI as one function block with the driver mapping in its own layer, guard every once-per-request action with an R_TRIG, and accept the block only when the watch table shows one command write per 200 ms tap at a 10 ms cycle with the amplifier off. If the AOI logic or the documented jog command for the AZD-AEP cannot be obtained, stop before the motor can move and request both from the supplier.
A notice screen for the same cell
Once the axis jogs from CODESYS, the cell usually wants a screen operators read on the way past: shift targets, changeover steps, safety notices. That screen is separate from the control logic. Our shop-floor displays run on 12 to 36 V DC, play content offline or run your own Android app, and carry an IP65 rating on the front face.
Questions
Is there an automatic way to import a Studio 5000 AOI into CODESYS?
No importer exists. The AOI lives in a Studio 5000 project format that CODESYS cannot read, so the interface and the logic are re-entered by hand, in any of the five IEC 61131-3 languages; structured text or ladder suits a jog block. Budget your time for the rebuild and the testing, not for tool hunting.
Where do AOI configuration parameters belong in the function block?
Declare them as VAR_INPUT entries with default values in the block, so every instance starts at the documented default. You can then override a default at the call site for one axis only, which keeps per-axis tuning out of the block logic and visible in one place.
How many R_TRIG instances does the jog block need?
One per edge you detect, each declared inside the block and called every cycle. Because the trigger lives in the block declaration, every instance of the block gets its own copy, so two axes never share edge memory even when the block code is shared.
Can two axes share one function block instance?
No. The instance is the memory: the R_TRIG states, counters and last command all live there. Two axes calling one instance overwrite each other, which shows up as a jog that fires or stops on the wrong axis. Declare one instance per axis, or an array of instances for a multi-axis cell.