An HMI event that fires exactly once from a PLC flag is missing its reset path, and the button works because your finger makes a fresh 0 to 1 transition. A 100 ms scan is not the cause. Hold the request bit until the panel writes an acknowledge bit back, then clear both and retest two full cycles.
The event fired once because the flag never came back to the state that arms the next one. The button works on every press because your finger makes a fresh 0 to 1 transition the event manager can see. A 100 ms scan is not the suspect here; it is the wrong question until the flag itself makes the transition the event's condition asks for. The fix lives in the PLC logic. Hold a request bit until the panel writes an acknowledge bit back, clear both, and every request fires exactly once, whatever the scan time and the panel's read cycle turn out to be.
Why one flag gives one event and a button gives every event
Event managers trigger in two ways. A change trigger fires when the tag moves, so 0 to 1 arms it and only a return to 0 rearms it. A level trigger fires while its condition is true. If the project uses a change trigger and the PLC sets the flag once and leaves it set, the tag never moves again and the manager has nothing to react to. The reset rung that should have cleared the flag never ran, or nothing in the project clears it.
The button tells you the trigger type by accident. Its press action writes 1 and its release writes 0, so every press hands the manager a fresh transition. That makes it a useful clue about the trigger type and a poor test of the PLC path, because the button object writes the tag through its own action. How long a panel holds its own bit under a finger is its own timing question; how many PLC scans an HMI momentary button bit stays on covers it.
What each symptom points to
Watch the flag in the PLC monitor and match what you saw to one of these.
- Flag goes to 1 and stays at 1. A change trigger with nothing new to see; the reset rung never ran. Find the logic meant to clear the flag and watch it online.
- Flag is 1 for one scan, then 0. The pulse fell between two panel reads. Hold a request until the panel acknowledges; the handshake below ends it.
- Flag cycles 0-1-0 cleanly and the second event still misses. Address mapping or the event's condition. Compare the address the event watches with the one you monitored.
- The button repeats the event, the PLC flag does not. Two different trigger paths. Compare the button's action with the event's condition and action.
Check the flag through one full cycle
Put the PLC online and watch the exact address the event is bound to. Trigger the sequence once and write down three values: the flag before the trigger, while the event should be active, and after the event should have completed. Open the event in the manager and read its trigger type, change or level. Check the action list there too and confirm nothing in it depends on the button object.
If the monitor shows the flag stayed at 1, stop there: the scan time is irrelevant and the repair is the missing reset rung. If the flag never made the transition at the address the event watches, compare the two addresses before anything else; HMI pings the PLC but reads fail: check the protocol driver sorts a dead link from a wrong tag. A clean 0-1-0 with a silent panel is the pulse width case, and the next two sections handle it.
Why the 100 ms scan is the wrong suspect
A coil that is on for one scan of a 100 ms cycle is visible on the wire for about 100 ms. The panel reads tags on its own clock, the read cycle set in the project's connection settings, and the two clocks run independently. A read catches the pulse only when a read lands inside that window, so the catch rate is pulse width measured against read cycle.
Shortening the scan moves the wrong number. A one-scan pulse shrinks with the scan, so a faster scan makes the panel's job harder. The worked example below puts numbers on both directions. The panel's read cycle is a setting on the panel side of the link; no PLC scan value sets it. Narrow pulses are the root cause, and the handshake removes the width question entirely. The same mechanism sits behind why an R_TRIG pulse never shows on the HMI screen.
The handshake: one request, one event
Two bits in the PLC do the whole job: a request bit the PLC writes and the panel reads, and an acknowledge bit the panel writes and the PLC reads. Name them whatever your project calls its handshake tags.
- Ready state: request = 0, acknowledge = 0.
- The PLC sets request to 1 and holds it there across scans.
- The panel reads request = 1 on its next cycle and fires the event, on that level or on the change to it.
- The event's last action writes acknowledge = 1 back to the PLC.
- A PLC rung sees acknowledge = 1 and clears request and acknowledge in the same scan.
- The pair is back at ready, and a change trigger is re-armed the plain way: the tag really did return to 0.
A request can never be missed, because it stays high until the panel's own acknowledge says it was read. One request can never fire twice, because request returns to 0 before the next one arrives. If the event repeats while request stays 1, the acknowledge rung is late: watch the acknowledge bit to confirm the panel's write reached the PLC, then check that the clear rung addresses both bits. The write-back wiring, including which side clears which bit, is laid out in signal an HMI alarm acknowledgment back to the PLC.
Recommendation: hold the request bit until the panel writes its acknowledge bit, and clear both bits from one PLC rung in a single scan. A change trigger and a level trigger both work on the request, because it returns to 0 before the next request arrives. Leave the scan time at the value the process logic was tuned to; change it only after the flag is shown to make the transition the event needs, and put it back after the test.
Worked example: a one-scan pulse against a 1 s read cycle
A packaging line counts finished batches. Its PLC runs a 100 ms scan, and one coil pulses for a single scan to make the panel log a batch event. The project sets the panel's tag read cycle to 1 s.
Pulse width: one scan, so about 100 ms. With pulse starts landing at random phases of the read cycle, a read catches the pulse 100 ms / 1000 ms = 10% of the time. Roughly one batch event in ten is logged; nine are lost with nothing on screen.
The line's engineer shortens the scan to 10 ms to help. Pulse width becomes 10 ms and the catch rate 10 / 1000 = 1%, one event in a hundred. The change moved the wrong way.
With the handshake: the PLC sets request and holds it. Worst case, the panel reads it up to 1 s later, fires the event, and the acknowledge write lands at the next slot up to 1 s after that; the PLC clears both bits within one 100 ms scan. Worst case from request to ready: 1 s + 1 s + 0.1 s = 2.1 s. Every request fires exactly once, and a faster read cycle only shortens that 2.1 s.
Test it before the line runs
Start from ready, request = 0 and acknowledge = 0, and let the PLC run two full request cycles. Watch all three signals: request, acknowledge, and the event's result on the panel. Pass means one request produced one event, the pair returned to ready, and the second request fired with nobody touching a button.
If the line has to run before the repair, a button on the panel can serve as a temporary operating method, and it is an operator override on a machine: use it only where the sequence stays safe with the event fired by hand, and log it as temporary. The handshake is the permanent repair, and the button path comes out of the project once it is in.
Questions
What if the panel cannot write a bit back to the PLC?
Let the PLC stretch its own pulse. Hold the flag on for a fixed number of scans instead of one: 20 scans at 100 ms keeps it visible for 2 s, which survives any panel read cycle set at 1 s or faster. Only then allow the reset, and build the hold from scan counts so the width never depends on the scan staying constant.
How do I measure the panel's real read cycle?
Pulse a test bit from the PLC and narrow the width until the panel stops catching it: try 500 ms, then 200 ms, then 100 ms. The narrowest width the panel reports reliably is the practical limit, and every real event pulse should stay at least twice that. The handshake makes the measurement unnecessary for the fixed event, but the number is quick to get on a legacy screen that cannot write bits back.
Can the handshake be made faster than 2.1 s?
Yes, and the read cycle is where the time is. Halve the panel's tag read cycle from 1 s to 500 ms and the worst case drops to 0.5 s + 0.5 s + 0.1 s = 1.1 s, because the two waits on the link shrink and the PLC scan is unchanged. Watch the panel's processor load after the change, since more reads per second costs time on both ends of the link.
Planning information, not legal or engineering advice. Rules differ by place: check codes and permits with your local authority and your licensed trades.