When the panel driver cannot map the PLC's string file type, store the ASCII characters in integer files, two bytes per word, and point the panel object at those words with its ASCII String data type. Keep one word block per direction, fix the byte order with a two-character probe, and test a four-character string before any real message.
The tag editor lists the data types the panel driver can map, and the PLC's string file type is missing from that list, so the text object has no source to point at and the tag will not bind. The direct route ends there, and the data route does not: an integer word is two bytes, and an ASCII character is one byte. Move the characters into the PLC's integer files, point the panel object at those words with its ASCII String data type, and the panel reads and writes text through a type the driver already supports. This article gives the layout, the two byte orders and how to tell them apart with a two-character probe, the word blocks for each direction, the test sequence, and the four symptoms this arrangement produces. Every value below is one you can read back in the PLC data table.
Why can't the panel map the PLC string file type?
Most panel drivers list the PLC data types they can map, and a string file type is often missing from that list, so the panel object has no legal source for your text and the tag refuses to bind.
The driver's type list is fixed: it carries the numeric types, sometimes a string type, and when the PLC's string file type (the ST file on compact PLCs is the common case) is absent, no object reconfiguration creates the mapping. The panel cannot read data its driver never fetches, so the tag fails to bind or the object stays empty. Stop working on the object and move the data. The PLC's integer files are a type the same driver maps without complaint, two bytes per word is enough to carry text, and the remaining panel work is a data-type change on one object.
How do I carry ASCII text in integer words?
Pack the characters two bytes per word: an ASCII character is one byte, a 16-bit integer word holds two of them, so a 20-character message occupies 10 words and a 40-character one occupies 20.
ASCII fixes the byte values: capital A is 65, the space character is 32, and the digits 0 through 9 are 48 through 57. An odd character count rounds up to the next whole word, and the unused last byte is padded with the space character, decimal 32, so nothing printable is lost and the display holds a fixed width.
One decision waits before any logic is written: which byte of the word carries the first character of each pair. That order is fixed inside the driver, and the two-character probe in the testing section below settles it with one entry and one data-table read. Record the result, because every word the PLC assembles afterwards uses that order.
Packing two ASCII bytes per word is the standard transport for text across a word-register interface; a FINS write that carries two ASCII bytes per word documents the same layout on another protocol. The move is also the same one that puts a float stored in two word registers on the panel: when the driver cannot map a type, hand it a layout it can.
Worked example: what do the words hold for a 20-character message?
A line-side message reading ORDER 1042 PALLET 07 is 20 characters, so it fills 10 integer words exactly, and each word carries one character pair as a decimal value you can check in the PLC data table.
Take the probe result as 16706, the first character high, so each word value is first character × 256 + second character. The pair OR works out as 79×256+82 = 20306, and the whole message runs:
| Word offset | Characters | Word value |
|---|---|---|
| +0 | OR |
20306 |
| +1 | DE |
17477 |
| +2 | R |
21024 |
| +3 | 10 |
12592 |
| +4 | 42 |
13362 |
| +5 | P |
8272 |
| +6 | AL |
16716 |
| +7 | LE |
19525 |
| +8 | T |
21536 |
| +9 | 07 |
12343 |
With the other probe result, 16961, every row swaps its two bytes: the first word becomes 82×256+79 = 21071 and the rest follow the same swap. Either way the block is 10 words at one start address, the object's element count is 10, and the panel shows ORDER 1042 PALLET 07.
Which words should the panel write, and which should the PLC write?
Give each direction its own block of integer words and record the two start addresses: one block for operator entry that the panel writes, one block for the message that the PLC writes, with no overlap.
The example blocks are 10 words each; size every block for its longest message and add a spare word if the text may grow. Two blocks cost two start addresses and buy clean tests: the entry path can be exercised while the message block sits untouched, and a PLC-side write cannot clobber an operator mid-entry. Keep the addresses the panel uses direct: the standing check for mapped integer data is to confirm the words are not indirectly addressed, the N100[N7:0] form, since the driver reads one fixed address and your layout hands it that address. If logic acts on the entered text, a batch ID that releases a transfer for example, validate its length and characters in the PLC rungs before acting: an entry object writes raw bytes, and a half-finished entry is a valid-looking wrong value.
How do I point the panel object at the integer words?
Set the object's data type to ASCII String, then give it the block's start address and the number of words it spans: an ASCII String object reads a vector of word values and shows each byte as a character.
An ASCII String display configuration asks for three things: the data type set to ASCII String, the start address of the block, and the number of elements, and it renders each byte in that span as one character. For the worked block that is the start address and 10 elements. The display object points at the PLC-written block and the entry object points at the panel-written block, so the two objects never touch the same words. If the object was first built as a numeric tag, changing the tag's data type without rebuilding every object keeps the rest of the screen untouched.
How do I test each direction with a short string?
Test the panel-to-PLC path first with a four-character entry such as ABCD, read the two written words in the PLC data table, then run the PLC-to-panel path with the same string assembled in logic.
- Type
ABCDinto the panel entry object and send it. - Read the entry block in the PLC data table. Word 1 reads 16706 with the first character high or 16961 with it low, since A is 65, B is 66, and 65×256+66 = 16706. Word 2 reads 17220 or 17475 to match, since C is 67, D is 68, and 67×256+68 = 17220.
- Assemble
ABCDin the display block from PLC logic with the recorded order, and confirm the display object shows ABCD. - Load the real message, the 10-word block from the worked example, and confirm the panel shows it character for character.
- When one direction works and the other does not, change only the failing direction's start address, element count and byte assembly. The passing direction is the reference for how the driver behaves.
What do the symptoms point to?
Each failure has one first cause to check before you touch anything else, and the table below pairs the four symptoms this arrangement produces with the setting or address that usually causes them.
| Symptom | First cause to check |
|---|---|
| The tag or object will not bind to the string file type | The driver's type list omits it. Move the text into integer words; the sections above carry the layout. |
| Numbers appear where characters should be | The object's data type is still a numeric type. Set it to ASCII String; a numeric object renders each word as a value. |
| Text is blank, truncated or scrambled | Compare the object's start address and element count against the block, then the recorded byte order against the assembly logic. |
| The word before the block holds two characters | The entry object's start address is one word low. The documented form of this off-by-one is ASCII entry writing the first two characters into a string-length word. |
A scrambled display with confirmed addresses and element count is byte order first: flip the assembly, rebuild the block, and compare against the example table. Numeric gibberish from a misread type is the same diagnosis with values, and nonsense numbers from a BCD analog register walks that case.
What does a working numeric tag prove?
A numeric tag that reads and writes correctly proves the cable, the driver and the address path work, so if strings still fail the fault is in the string object's data type or word layout, not the link.
That is why none of the checks above touch cabling, protocol settings or the network: the numeric tag already exercises them. It does not prove the string layout, because the string object adds a data type and a byte order a numeric tag never uses, and that is exactly what the ABCD probe isolates. Work one direction at a time, keep the two start addresses and the byte order in the project notes, and the next string on this machine is a five-minute change.
Recommendation: When the panel driver cannot map the PLC's string file type, stop reconfiguring the object and move the text: characters into integer words two bytes per word, the object's data type set to ASCII String with the block's start address and word count, one word block per direction, and the ABCD probe run in both directions before any real message reaches the screen.
This stays an HMI tag fix. A standalone board beside the line for shift notes, counts and targets is a different screen with a different job, and the shop-floor displays page covers that one.
Questions
How many integer words does a longer message need?
Divide the character count by two and round up. A 21-character message fills 11 words, and the unused last byte takes the space character, decimal 32. Reserve the block for the longest message the screen will show plus one spare word, so a future edit cannot write past the block, and keep the object's element count at the configured block length so the panel never reads words outside the reservation.
Why does a one-character edit move the word value by 256?
The first character of each pair sits 256 times heavier than the second when the probe returned 16706 for AB. Change the second character from B to C and the word moves from 16706 to 16707; change the first character from A to B and it jumps 256 to 16962. To decode a word, divide by 256: the quotient is the first character, the remainder is the second, and both should land in the printable ASCII range of 32 to 126.
Can the panel and the PLC share one block for both directions?
Only with the PLC owning the timing. The logic must copy the entry words into its own tags and clear its ready flag before the panel is allowed to write again, and the panel must never write the display block. Without that handshake a failed transfer overwrites the message on screen, and the two directions cannot be tested apart. Two start addresses are cheaper than that debugging.
Does a driver update ever make the string file type mappable?
It can. Driver releases add mappable types over time, so after an update check the driver's type list for the PLC's string file type before rebuilding anything. If it appears, map the object directly and retire the word blocks and the assembly logic. Keep the integer-block notes until the direct mapping has survived one real message in both directions, because a type that maps is not the same as a layout that matches.
Planning information, not legal or engineering advice. Rules differ by place: check codes and permits with your local authority and your licensed trades.