A dialog opened by name from IEC code has no compile-time dependency, so CODESYS leaves it out of the visualization download and FbOpenDialog finds nothing on the controller. Tick the dialog on the Visualizations tab of the Visualization Manager and do a full download. For a library with many dialogs, one reference visualization pulls them all in.
Open the Visualization Manager in your application, tick the checkbox for the dialog on the Visualizations tab, then run Clean all, Build and a full download. That is the whole fix when a POU calls FbOpenDialog or FbOpenDialogExtended from the VisuUtils library and no dialog appears: the name travels as a string literal such as 'DlgConfirm', a string creates no compile-time dependency, and CODESYS leaves the dialog out of the visualization download. The block searches the downloaded set at runtime, finds nothing under that name, and returns quietly with xDone set. The whole job takes under 5 minutes on one project. This page maps the symptoms, gives the checks on the call itself, and shows the pattern that handles a library full of dialogs.
Why the code runs and no dialog appears
CODESYS does not download every visualization object in the project tree. The visualization download is built from a dependency set that the compile step assembles from 4 sources:
- the visualization start object
- frames and tab controls placed on a downloaded visualization
- the targets of an element's
Open dialoginput configuration - the objects ticked in the Visualization Manager
A dialog name inside an IEC string literal is in none of those sources. The object stays in the project, the build finishes clean in under 30 seconds on a mid-size project, and the dialog is absent from the controller.
This also explains the classic symptom: the same dialog opens from a button. The input configuration resolves the dialog at compile time, which is one of the 4 sources, so the button forces the dialog into the download. Your POU has no such helper, and nothing in the build tells you so.
Symptoms and what each points to
- The dialog opens from a button on the screen and never from code. The object is on the controller, because the button pulled it in. The fault is in the call: name,
bExecuteedge, or client. - The dialogs stopped appearing after a move into a library. Nothing in the newly referenced library creates a compile-time reference, so the dialogs dropped out of the download. Tick them.
- The code works on the first controller and fails on a second. Each application carries its own Visualization Manager selection, so the second application never had the tick.
- A breakpoint shows the block called every cycle in a 10 ms task with the right name. The call is sound; treat the download as the suspect.
xDonegoes true and no dialog appears. The request was processed. Check the name qualification and the client selection before touching the download again.
A serial port that refuses to open has the same shape, code correct and a configuration object missing; that case is COM.Open error 5004 on a serial port.
The fix: tick the dialog and download in full
- In the device tree, double-click
Visualization Managerunder your application. - Open the
Visualizationstab. It lists every visualization object the application sees, including dialogs supplied by referenced libraries. A library with 40 dialogs fills one list; you tick only the ones your code names. - Find the dialog your code names, for example
DlgConfirmorMyLib.DlgConfirmwhen it lives in a library namespace. Its checkbox is cleared; that cleared box is the whole fault. - Tick it. Repeat for every dialog your POUs open by name.
- Save, then run
Clean all,Build, and a fullDownload. An online change is the wrong tool for refreshing the visualization set. - Start the application and trigger the POU path again.
The manager also carries a Dialog Settings tab. That one presets the standard dialogs for the client, such as login and user management. A dialog your code opens by name needs the Visualizations tab, not this one.
Four checks on the call itself
Run these before you blame the download, and again if the tick alone does not cure the line. Budget 10 minutes for all four.
| Check | What it must be | What happens when it is wrong |
|---|---|---|
stDialogName input |
The exact object name, case included, qualified with the library namespace when the dialog lives in a library, e.g. MyLib.DlgConfirm |
The lookup finds nothing and no dialog opens |
bExecute input |
TRUE on the scan in which the block is called; a pulse cleared 1 scan early never reaches it | The block never sees the request |
| Instance call | Called every cycle from a task that runs, so at a 10 ms cycle interval the state machine always advances; the block steps through a state machine | The request latches and nothing processes |
| Client | A visualization client of this application that presents dialogs | The dialog opens for no one |
One reference visualization for a whole library
Ticking boxes works until the dialogs come from a library. The boxes live in each application's manager, so every project that reuses the library repeats the work. Move the dependency into the project instead.
Create 1 service visualization that nobody displays. Place every dialog your code opens as a frame on it, or give one element an Open dialog input configuration per dialog. Frames and input-configuration targets are both in the dependency set, so the compile step pulls those dialogs into every download that includes the visualization. Package the POU code and this visualization together in your own library, and the dependency travels with the code.
| Approach | Cost | Where it fits |
|---|---|---|
| Tick list in the manager | 1 checkbox per dialog, per application | Few dialogs, one project |
| Reference visualization | 1 extra object, 1 frame per dialog | Dialogs from a shared library, several projects |
| Wrapper library around code and visualization | Library maintenance and version discipline | A standard block reused across a plant |
Mark the string dependency in the code
Nothing in the project flags a cleared box, because the only link between the POU and the dialog is a string. Put a comment at each call site with the dialog name, the fact that it is opened by name only, and the tab that must stay ticked. Whoever reworks the project next then knows what that box controls.
Example: four dialogs from a shared library
A plant moves its operator confirmations into one shared library. The library carries 12 dialogs; the packaging line's sequence program opens 4 of them by name through FbOpenDialog in a 20 ms cycle task. The week after the move, buttons on the main screen still open their dialogs and all 4 code-opened dialogs do nothing.
The Visualizations tab confirms the diagnosis in about 5 minutes: 4 cleared checkboxes on library dialogs. Ticking them cures this application today, but the plant runs 3 projects on that library, so the manual route is 3 x 4 = 12 tick entries to keep current.
The plant instead builds 1 reference visualization with 4 frames, one per dialog, and includes it in each project. That is 1 object replacing 12 entries. After a Clean all, Build, and full Download on each of the 3 controllers, taking about 15 minutes total, all 4 dialogs open from code on all 3 projects.
Recommendation: tick boxes by hand while fewer than 5 dialogs are opened by name in a single project. From the moment those dialogs live in a library that more than one project uses, build 1 reference visualization with a frame per dialog and let the dependency analysis carry them into every download.
How to verify the cure
- Reopen the
Visualizationstab after saving. A box that reads cleared again means the save landed after the download; save first, then download. - Log in and confirm the application is not in a changes-pending state. A full
DownloadafterClean allandBuildis what regenerates the visualization set. - Put
xDoneandxErrorof the block instance in a watch list. A completed request with no dialog points at the name or the client, and away from the download. - Add a temporary button with an
Open dialoginput configuration on the same dialog name and download. If the dialog appears from the button, the name is right and the client can present dialogs, and the button itself is what pulled the object in. Keep that button as the permanent compile-time reference, or replace it with the tick. - If a dialog gates a safety-relevant acknowledgement, recheck the tick after every download. The failure mode is silence, and silence is a poor alarm.
When the message belongs on a second screen
Some dialogs exist to tell people something, and the people who need the message never touch the HMI. A status the operator confirms in a dialog is often worth a separate read-only screen at the line; the choice is laid out in live factory data display: signage or dashboard, and the mounting and power questions sit with shop-floor screens.
Questions
What is the difference between the Visualizations tab and the Dialog Settings tab?
The Visualizations tab decides which dialog objects are compiled into that application's visualization download, including dialogs supplied by referenced libraries. The Dialog Settings tab presets the standard dialogs for the client, such as login and user management. A dialog your code opens by name needs the checkbox on the Visualizations tab; the built-in dialogs are handled on Dialog Settings.
Is there a setting that downloads every visualization at once?
Some versions and profiles expose a manager-level option to include all visualizations in the download. Check whether yours has it before designing around it, because availability varies with the version and the visualization profile. It also produces the largest download and boot project on the target. The reference visualization is the portable route, because it relies only on the dependency analysis that every version performs.
Do the ticks survive a project copy or a library update?
Treat the selection as belonging to a single application. A project that pulls the library in starts with its own cleared manager, and a library version change is the moment to open the tab again, because dialogs that arrive with the update come unticked. A reference visualization ends the housekeeping: the frames carry the dependency into any project that includes them.