A bitmap drawn over live PLC values can slow every number and indicator light on that screen. Hide the drawing in a project copy first, then turn off transparency you do not need, set the poll period to 5 to 10 ms (1 to 2 ms if it was 0), and watch the Ethernet link for lost packets. Change one setting at a time and keep the single change that restores response.
A compressor drawing behind live values should cost nothing, yet on some panels it costs the whole screen: thermocouple numbers and indicator lights crawl with the graphic in place and snap back the moment it comes off. The PLC is almost never the fault. Work down this order and change one setting at a time: hide the bitmap in a project copy, turn off transparency you do not need, set the poll period to 5 to 10 ms, and watch the Ethernet link for lost packets. One installation dragged exactly this way with a 75 kB drawing on an 8-inch panel, with the newest panel software installed. A small file and a current runtime do not settle the question. Each test below takes minutes, and one of them ends with a setting you can keep.
What each symptom points to
- Slow values and lights only on the screen that carries the drawing. Rendering load. The panel is spending its refresh time on the graphic; the hide-the-bitmap test below settles it in minutes.
- Every screen is slow, drawing or no drawing. The link or the poll period, not the bitmap. Check the packet counters first, then the poll setting.
- The poll period is set to 0 ms. The panel is firing requests as fast as it can, and a heavy screen makes that worse. Test a small fixed period: 1 to 2 ms.
- The poll period is 100 ms or more. Every value on that screen refreshes only as often as the period allows, 10 updates per second at best at 100 ms. Test a faster period in the 5 to 10 ms range.
- Lost packets or climbing retry counts in the link diagnostics. The network path. Fix that before touching the project again.
Hide the bitmap in a project copy
Run this test on a copy of the project, on a screen the operator is not relying on; an edit on the live screen can hide a real alarm while you watch.
- Record a baseline. Pick one thermocouple value and one indicator light, and time how long each takes to change on the affected screen. A 30-second video of the screen works as the record.
- Save a copy of the project and open the copy.
- Hide or delete the drawing on that screen. Leave every value field, indicator light, PLC address and communications setting exactly as it is.
- Load the copy to the panel and repeat the 30-second observation under the same conditions. Repeat once more if the drag comes and goes.
- If response recovers with the drawing gone, the rendering of that graphic is the load; continue with the transparency check. If nothing changes, put the drawing back and move to the poll period and the link.
Do not clear the bitmap as a suspect just because the file is small. Pixel dimensions, file format and transparency weigh more than kilobytes, which is why the tests below take each apart separately.
Turn off transparency you do not need
Transparency is the most expensive thing a bitmap can carry. Panel vendors say as much in their own support pages: a runtime responds slowly when it has to process large bitmaps with transparency, transparent graphics have been documented turning black after a firmware upgrade until the transparency option is switched per graphic, and transparent elements have been documented losing their transparency at random until a refresh is forced.
In a project copy:
- Find the transparency setting on the graphic object, or in the project's graphics resources; your project software's manual names the exact spot.
- Turn it off, load the copy, and retest against the baseline.
- If the drawing must blend into the screen, export a copy whose background colour matches the screen background and drop the transparency entirely. The screen looks the same and the panel has no blending to do.
Older project formats carry extra traps with BMP and GIF transparency; bitmap transparency limitations and workarounds for BMP and GIF files covers the common ones. When the drawing has to update live instead of sitting still, a documented caching setting can change the behaviour completely: NumCachedImages 0 for live bitmap updates.
Worked example: a 75 kB drawing on an 8-inch panel at a 100 ms poll period
Inputs, and where each comes from:
- Poll period as configured: 100 ms, read from the project's communication settings; the kind of high value worth testing downward.
- Drawing: about 75 kB, drawn on the screen background, transparency off (from the installation that showed this fault).
- Panel: an 8-inch touch panel talking to the PLC over an Ethernet card (from the same installation).
- Test values: 5 ms and 10 ms; 1 to 2 ms only where the period was 0.
The rule in words: a poll period of P ms asks the PLC for fresh values once every P ms, so the screen gets 1000 ÷ P update chances per second, whatever is drawn on it.
Arithmetic:
- 1000 ÷ 100 = 10 updates per second at the 100 ms setting.
- 1000 ÷ 10 = 100 updates per second at the 10 ms test value.
- 1000 ÷ 5 = 200 updates per second at the 5 ms test value.
- 200 ÷ 10 = 20, so going from 100 ms down to the 5 ms test value puts 20 times the transactions on the link.
Result: at 100 ms, every value and light is at most 10 updates per second fresh, and an indicator light that steps faster than that cannot be seen to step at all. At the faster test values the same screen gets 100 to 200 updates per second, enough to keep lights and numbers current as long as the link carries the load.
Decision: if the configured period sits above 20 ms, which is under 50 updates per second (1000 ÷ 20 = 50), and the screen drags, move it to the 5 to 10 ms range and retest. Once you sit there with zero lost packets, polling has headroom and a still-slow screen points at the drawing; go back to the transparency check. Keep the period at or above 1 ms: at 1 ms the panel would fire 1000 requests per second, and that can swamp a small PLC's link.
Set the poll period and watch the link
The poll period sits in the project's communication settings. The panel's configuration software carries the link diagnostics beside it.
- Record the configured period and the diagnostics counters: errors, retries, disconnects.
- Change only the period. From 0 ms, test 1 to 2 ms; from 100 ms, test the faster values from the example. If the software rejects a value, use the smallest it accepts.
- Retest against the baseline, then read the counters again. New errors at the faster period mean the link or the PLC is at its limit; restore the original value.
- The period is not the whole story. Every extra panel on the link multiplies the transaction count, which connecting many operator panels to one PLC works through, and the poll structure matters too when one panel reads two PLCs: one HMI reading two PLCs.
| What you see | What it points to | Next check |
|---|---|---|
| Lost packets or climbing retries while the drawing is on screen | The network path, not the drawing | Fix the path first: cable, switch port or the Ethernet card |
| Period at 0 ms | No pacing at all | Test 1 to 2 ms |
| Period at 100 ms or higher | Values refresh 10 times per second at best | Test the faster range from the example |
| Faster range, zero lost packets, still slow | Rendering load | Back to the bitmap and transparency checks |
| Faster polling adds errors | The link or PLC is at its limit | Restore the original period |
A device that stops answering the link altogether is a different fault: HMI no communications when one PLC model fails walks through that case.
Make the change hold
Apply to the production project only the one change that restored response, with the original project saved untouched. Verify during normal operation with the drawing on screen, and read the packet counters once more after a full shift. Write down the before and after: poll period, project version, panel model and screen size, bitmap file size and format, transparency state, packet counts.
If no single change isolates the drag, send the project and that record to the panel vendor's support desk; that beats more blind edits on a machine in production. If the drawing cannot stay without the delay, run the simplified screen temporarily and have the project reviewed.
Do not keep shortening the poll period to mask a rendering load: 1 ms is a test value. Once the cause is fixed, step the period back up to the slowest value that keeps the screen current, usually somewhere in the 5 to 10 ms band on a link this small.
If the conclusion is a new panel for the operator, the HMI stays the HMI. Our panel-mount Android displays are built for a separate status or notice board next to the machine, not as a replacement for the panel running it.
Recommendation: test in this order, one change at a time: hide the bitmap in a project copy; if response recovers, turn off transparency you do not need and match the drawing's background colour to the screen background; if the bitmap is not the cause or transparency is already off, set the poll period to the faster range from the worked example (1 to 2 ms from 0) and watch the link for lost packets. Keep whichever single change restores response for a full shift and return every other setting to its original value.
Questions
Is 1 ms a good poll period to keep once the screen is fast?
Treat 1 to 2 ms as a test value, not an operating value. At 1 ms the panel asks for values 1000 times per second, far more traffic than one screen needs. Once the real cause is fixed, step the period back up from 5 ms until a value or light starts to lag, and run there. The slowest period that keeps the screen current is the easiest on the link and the PLC.
Does a drawing on the background screen slow every screen in the project?
It can. A screen built on a background that carries the bitmap loads that drawing each time it opens, so several screens can share one rendering load. Run the same hide-and-compare test on the background screen itself. If response recovers across the project, the shared background is the load; simplify the drawing or match its background colour to the screen colour so transparency is not needed.
What should be ready before calling the panel vendor's support line?
Send the project file; the settings live in it, so support will ask for it anyway. With it, include the poll period as configured, the panel model and screen size, the project software version, the bitmap's file size, format and transparency state, and the diagnostics counters before and after each test. That set of numbers usually turns a week of guessing into one reply.
Planning information, not legal or engineering advice. Rules differ by place: check codes and permits with your local authority and your licensed trades.